BCD-87-004-PE

                                                       4-0210 -1 378-2

 

                                STATE OF MINNESOTA

                        OFFICE OF ADMINISTRATIVE HEARINGS

 

                     FOR THE MINNESOTA BUILDING CODE DIVISION

 

In the Matter of the Appeal

of Weber Barlow Stores, Inc.                                FINDTNGS  OF FACT,

and Weis Builders, Inc. of                                 CONCLUSIONS AND

the Final Decision of the                                  RECOMMENDATION

City of Rochester

 

 

    The above-entitled matter came on for hearing before   Administrative Law

Judge Peter C. Erickson on April 8, 1987 at the  Olmsted  County  Courthouse,

Rochester, Minnesota and on April 10, 1987 at the  Office  of  Administrative

Hearings, 400 Summit Bank Building, 310 Fourth Avenue South, Minneapolis,

Minnesota.  The final post-hearing brief was filed on May 21, 1987, at which

time the record was closed.

 

    Steven K. Champlin, from the firm of Dorsey & Whitney,  2200  First  Bank

Place East, Minneapolis, Minnesota 55402, appeared on behalf of the

Appellants, Weber-Barlow Stores, Inc. and Weis Builders, Inc.  Douglas J.

Gregor, Assistant City Attorney, Room I City Hall,  Rochester,  Minnesota  55902,

appeared on behalf of the Respondent, the City of Rochester

 

    Notice is hereby given that, pursuant to Minn.  Stat.  14  61  the  final

decision of the Commissioner of Administration shall not be made until this

Report has been made available to the parties to the proceeding for at least

ten days, and an opportunity has been afforded to each party adversely

affected to file exceptions and present argument to the Comissioner.

Exceptions to this Report, if any, shall be filed with Commissioner Sandra J.

Hale, Administration Building, 50 Sherburne Avenue, St.  Paul,  Minnesota  55155,

 

                               STATEMENT OF ISSUES

 

    The issues to be determined in this proceeding are whether:  (1) the

Appellants failed to comply with the fire protection  requirements  contained  in

U.B.C.  1712; and (2) the City is estopped from alleging a violation of

U.B.C.  1712,

 

    Based upon all of the proceedings herein, the  Administrative  Law  Judge

makes the following:

 

                                 FINDINGS OF FACT

 

    1.   Weber Barlow Stores, Inc. ("Weber Barlow"), contracted  in  December  of

1985 with Weis Builders, Inc. ("Weis Builders"), a general contractor

operating out of Rochester, Minnesota to design and build a Cub Retail Center

within an existing building located at 1021-15th Avenue Southeast in Rochester.

 


    2.   The Cub Retail Center construction project included design and

             of a Cub Foods supermarket.  Approximately 7,000  square  feet  of

the Cub Foods supermarket floor space is occupied by freestanding  cooler  and

freezer units.' The coolers and freezers (hereinafter only  "coolers")  are

constructed with pre-manufactured insulation panels using a foam plastic

material which has a flame-spread rating of 20 and a "smoke developed"  rating

   300.  The foam plastic is sandwiched between two layers of corrosion-

resistant stainless steel, each having a Lase thickness of 0.016  inches.  The

insulation panels are four inches thick, eight feet wide and 25 feet  long.

foam plastic material is considered a fire hazard because of its rapid  fire

spread, dense smoke and "off-gassing", the emission of toxic gasses  during

 burning or disintegration.

 

    3.   Weis Builders submitted an application to the City of Rochester,

building Code Division on February 13, 1986 for a building permit for the  Cub

Store construction project together with the plans and specifications for  the

work covered by the permit.

 

    4.   The plans and specifications provided to the City included a

 footprint" of the areas where the coolers would be placed within the  building

and a cross-sectional detail of the area above the coolers identified with  the

phrase "cooler or freezer NIC" (not included in the contract).  The  sprinkler

plans did not identify the location of the coolers and freezers, but  could  be

cross-referenced by section numbers to the "footprint" plans.

 

    5.   On February 25, 1986 the Building Code Division issued the first in  a

series of inquiries with respect to the permit application.  Weis  Builders  was

  juested to "address the requirements for a thermal barrier if  foam  plastic

insulation is used in the coolers or freezers in accordance with the

requirements of UBC, Section 1712 A and B." Weis Builders responded  to  the

City's inquiry by letter dated March 10,, 1986 stating that  "all  freezers

   ply with the requirements of foam plastic insulation.  All coolers are

 'Pal laminated maintaining fire resistance."

 

    6.   The permit for the construction project was issued by the City  of

Rochester on March 26, 1986 without further correspondence between the  parties

  in respect to the adequacy of the fire protection for the cooler units.

 

    7.   Weis Builders subcontracted with Olympic Fire Protection  ("Olympic")

to install the sprinkler system in the Cub Retail building.  Olympic  prepared

and submitted sprinkler system plans and drawings to the City of  Rochester,

building Code Division which were approved on July 24, 1986.

 

    8.   The City's approval stamp of the building permit plans and the

sprinkler system plans indicates that the approval "should not be  construed

as . . . a determination by [the City] that these plans comply with all

requirements of the Building or Fire Code. . . . The owner and his  contracting

agent are responsible for meeting all code requirements and should  deviations

 subsequently be determined or discovered, the owner and the contracting  agent

will be required to make necessary corrections  or  additions."  Additionally,

 

 

    'A small portion of the 7,000 square feet of cooler and freezer  space  is

not at issue in this proceeding.

 

                                       2 -

 


in a letter dated July 24, 1986 from the City Fire Prevention Bureau to

Olympic, the City stated  that  final  approval  of  the  sprinkler  system  was

subject to an on-site inspection.

 

    9.    On or about September  17,  1986,  and  approximately  two  weeks  before

the opening of the Cub Retail  Center,  the  City  made  its  final  inspection  of

the building.  At  that  time,  the  Building  Inspector  for  the  Fire  Prevention

Bureau of the  City  of  Rochester  indicated  to  Weis  Builders  representatives

that the building construction  violated  the  requirements  of  U.B.C.    1712  (a)

and (b) because the area immediately above  the  coolers  on  the  west  side  of  the

building was not sprinklered.  All  other  areas  of  the  store  were  covered  by  an

automatic sprinklering system, as was the interior of all the onolers.

However, the area immediately above the coolers on the west side of the

building below the second floor was not covered.

 

    10. The cooler units  are  located  along  approximately  225  feet  of  the  west

side of the Cub Foods  supermarket,  Along  the  east  wall  of  the  supermarket  are

a number of exit/entrances  into  the  Cub  Center  main  retail  area.  In  the

middle of the supermarket is  a  twenty-foot  wide  corridor  leading  to  an  outside

exit.  On the north end is  a  stairway  to  the  floor  above  which  contains  an

office area.

 

    11. The area between the  top  of  the  coolers  and  the  first  floor  ceiling

(the floor of the second story)  is  a  space  approximately  22  inches  in  height.

The masonry exterior walls of the  building  form  the  back  side  of  the  space.

The top surface of the coolers form  the  floor  of  the  space  and  are  separated

from the back masonry walls by approximately 6 - 10 inches of space.  The

ceiling of the space is the  metal  decking  and  two-inch  concrete  floor  of  the

building's second story, Between  the  ceiling  and  floor  of  the  space  are  steel

trusses, approximately 6  inches  from  the  surface  of  the  coolers.  Also  within

this area are various  utility  lines  and  two  sprinkler  water  supply  lines

running the length of the  cooler  units  which  supply  water  to  the  sprinkler

heads which extend  down  into  the  coolers  themselves.  Subsequent  to  the  Notice

of Violation dated  September  26,  1986,  the  Appellants  affixed  5/8-inch  thick

gypsum board vertically at the front of  the  space  from  the  top  of  the  coolers

and reaching to the  concrete  floor  above,  Pipes  and  metal  beams  run  through

the gypsum board and an access door has been cut.

 

    12. Weis Builders  responded  to  the  City  by  letter  dated  September  17,

1986, contesting the need  for  sprinkler  protection  in  the  area  above  the

coolers.  The City of  Rochester  issued  a  violation  notice  to  Weis  Builders  on

September 26, 1986 and again on January 23, 1987 because of the continued

failure  to provide sprinkler protection in the area above the coolers.

 

    13. Appellants estimate  that  the  cost  of  installing  sprinkler  heads  or  a

thermal  barrier which would comply with  U.B.C.    1712  in  the  area  above  the

coolers  would  be  approximately  $11,000.  The  total  value  of  the  construction

project  as estimated on the permit application was $1,000,000.

 

    14.  Three  construction  projects  in  the  metropolitan  area  which  Weis

Builders has worked  on  have  pre-manufactured  cooler  units  installed  with  a

small space between the tops of the coolers and the second floor of the

buildings.  These spaces have  not  been  required  to  be  sprinklered  by  the  local

inspectors (Maplewood, Eden Prairie and Brooklyn Park).  However, the

municipalities of Austin  and  Albert  Lea  require  that  sprinklers  be  installed

above all coolers which are manufactured with foam insulation.

 

                                          3-

 


    15.  Weis Builders appealed the alleged violation to the Rochester

building Code Division Board of Appeals which resulted in a hearing on

October 7, 1986.  On October 9, 1986, the Board of Appeals notified Weis

Builders that the violation notice would be withdrawn, concluding that the

--ea in question was not required to be protected by a sprinkler  system

  however, on November 7, 1986, the Board of Appeals sent a notice to Weis

builders that it had reversed its ruling on this issue and that the violation

notice would be upheld.  On December 3, 1986, Weis Builders and  Heber  Barlow

 appealed this decision to the Commissioner of Administration pursuant to Minn.

stat.  16B.67.

 

    Based on the foregoing Findings of Fact, the Administrative Law Judge

makes the following:

 

                                  CONCLUSIONS

 

    1.   The Administrative Law Judge and the Department of Administration

have jurisdiction over this matter pursuant to Minn.  Stat.  16B.67 and 14.50

,1986).  The Notice of Hearing was proper in all respects.  The Department has

complied with all procedural and substantive provisions of law or  rule.

 

    2.   The Appellants have failed to meet the requirements of U.B.C.  1712

in the Cub Foods retail supermarket.

 

    3.   The City of Rochester is not estopped from requiring the  Appellants

to implement corrective fire protection measures.

 

    Based upon the foregoing Conclusions, the Administrative Law Judge  makes

the following:

 

                                 RECOMMENDATION

 

    IT IS HEREBY RECOMMENDED that the Commissioner of the Department  of

Administration issue an Order upholding the violation issued by the City of

Rochester which requires Appellants to implement appropriate  corrective

  isures to comply with U.B.C.  1712.

 

Dated this day of June, 1987.

 

 

 

 

                                         PETER C. ERICKSON

                                         Administrative Law Judge

 

 

 

                                     NOTICE

 

    Pursuant to Minn.  Stat.  14.62, subd. 1, the agency is required to serve

its final decision upon each party and the Administrative Law Judge by  first

CL ass mai I .

 

Reported:  Transcript Prepared by Earl M. Steen and Associates.

 

                                       4 -

 


                               MEMORANDUM

 

The relevant portions of the Uniform Building Code read as follows:

 

     Foam Plastic Insulation

 

          Sec. 1712.  (a) General.  The provisions of this

     section shall govern the requirements and uses of  foam

     plastic in buildings and structures.  For trim, see

     Section 1705(e).

 

          Except where otherwise noted in this section, all  fOAm

     plastics used in building construction shall have a  flame-

     spread rating of not more than 75 and shall have a  smoke-

     developed rating of not more than 450 when tested in  the

     maximum thickness intended for use in accordance with

     U.B.C. Standard No. 42-1.  All packages and  containers  of

     foam plastic ingredients shall bear the label of an

     approved agency showing either the flame-spread rating  and

     smoke-developed rating of the product at the  thickness

     tested or the use for which the product has been  listed.

     The interior of the building shall be separated from  the

     foam plastic by an approved thermal barrier having an  index

     of 15 when tested over calcium silicate board in  accordance

     with U.B.C. Standard No. 17-3.  The thermal  barrier  shall

     be installed in such a manner that it will remain in  place

     for the time of its index classification based upon

     approved diversified tests.

 

          (b) Specific Requirements.  Unless  otherwise  speci-

     fically approved as provided by Section 1712(c) or by  other

     sections of this code, foam plastics may be used as follows;

 

          1. Masonry or concrete  construction.  Foam  plastics

     may be used without the thermal barrier described  above,

     regardless of the type of construction, when the foam

     plastic is covered by a minimum of 1-inch thickness  of

     masonry or concrete in a wall, floor or roof system,

 

          2. Attics and crawl spaces.  Within an  attic  or  crawl

     space where entry is made only for service of  utilities,

     foam plastics shall be protected against ignition by  1-112-

     inch-thick mineral fiber insulation, 1/4-inch-thick  ply-

     wood, hardboard or gypsum wallboard,  corrosion-resistant

     sheet metal having a base metal thickness not less than

     0.0160 inch at any point, or other approved material

     installed in such a manner that the foam plastic in not

     exposed.

 

          3. Cold storage construction.  Foam  plastic  installed

     and meeting the requirements of (a) above when tested in  a

     thickness of 4 inches may be used in a thickness up  to

     10 inches in cold storage buildings, ice plants,  food-

     processing rooms and similar areas.  For rooms within a

     building, the foam plastic shall be protected by a  thermal

     barrier on both sides having an index of 15.

 


              Foam plastic insulation may be used in freentanding

         coolers and freezers without the thermal barrier when the

         foam plastic has a flame-spread rating of 25 on less when

         tested in the thickness intended for use, is covered by  not

         less than 0.032 inch of aluminum or corrosion-renistant

         steel having a Vase metal thickness not less than 0.0160

         inch at any point and is protected by an automatic

         sprinkler system.  When such a cooler or freezer is within

         a building, both the cooler or freezer and that part of  the

         building in which the room is located shall be  sprinkled.

 

    As set forth above, Section 1712(a) states a general requirement that  foam

plastics shall be protected from fire hazard by the use of an approved  thermal

barrier.  Specific requirements are set forth in paragraph (b) of  that  section

regarding the use of foam plastic insulation in cold storage construction.

"that provision requires that foam plastics either be protected by the use of  a

thermal barrier or that the "part of the building in which the room is  located

shall be sprinklered."  Subparagraph (b)2. provides for a specific exclusion

or crawl spaces which would not require either a thermal barrier  or

sprinklering in the case herein.

 

    The specific Code issues which have been litigated in this case  are:

(1) whether U.B.C.  1712(b)3. requires sprinklering on the top surface of  the

coolers as well as the surrounding area and interior; (2) whether the floor  of

the second story, located 22 inches above the top of the coolers,  in

conjunction with the gypsum board enclosure, constitutes a thermal barrier

thin the meaning of U.B.C.  1712(a); and (3) whether the space above  the

 coolers constitutes a "crawl space" within the meaning of U.B.C.  1712(b)2.

 

    Appellants first argue that U.B.C.  1712(b)3. should not be read  to

    ire sprinklering on the top of the coolers as well as the surrounding orea

    interior.  That provision reads that "both the cooler or freezer and that

part of the building in which the room is located shall be  sprinklered."

Appellants read the word "room" to mean the area of the building in which the

cooler is located rather than meaning the cooler or freezer itself.  The  Judge

   agrees with that interpretation.  The rule provision  specifically  states

that "foam plastic insulation" must be "protected by an automatic  sprinkler

system."  This provision must be read to require that all sides of the

 igulation panels, including the interior of the cooler room, must have

sporinkler protection.  Consequently, the Judge concludes  that  U.B.C.

  1712(b)3. requires sprinkler protection on the top of the coolers  herein.

 

    Appellants next argue that the second story floor, which is only 22  inches

 love the top of the coolers, constitutes a thermal barrier within the  meaning

of  1712(a) in conjunction with the gypsum board enclosure.  However, the

language in paragraph (a) can only be read to require that the thermal  barrier

first be attached to the foam plastic insulation material itself.  This

  interpretation is supported by a discussion of the testing techniques

contained in the 1976 analysis of revisions published by the ICBO which

requires that the "15-minute thermal barrier be applied over the  plastic

material." Thus, the Judge has concluded that the second story  floor  "thermal

 Trier" does not fulfill the requirements contained in U.B.C  1712.

 

 

                                       6-

 


    Next, Appellants argue that the space above the coolers  constitutes  a

"crawl space" within the meaning of U.B.C.  1712(b)2. and thus,  requires  no

fire protection either by use of a thermal barrier or sprinklering.  The

U.B.C. does not provide a definition of "crawl space" except to refer to  it  in

paragraph (b)2. as an area "where entry is made only for service of

utilities." A generally accepted definition of the term "crawl  space"  is  a

space between the ground and the first floor of a building which  is  surrounded

by the building foundation wall.  Tr.  Vol. 2, p.  76,  Appellants  argue  that

the area in question above the coolers is not used for any purpose  other  than

to "service" the utility lines running through the 22-inch space

 

    Although the "crawl space" exception could be stretched to apply  to  the

case herein, the Judge does not accept the resulting analysis that no fire

protection is required.  Section 103 of the U.B.C.  states  specifically  that

the most "restrictive" provision of the Code shall govern  where  requirements

appear to conflict.  In this case, paragraph (b)3. speaks  specifically  to  the

use of foam plastics in cold storage construction.  Subparagraph 2,  is  a  more

general requirement for the use of foam plastics in "attics and crawl

spaces".  Thus, the more restrictive requirements contained  in  subparagraph  3,

must apply herein.

 

    Finally, the Appellants have argued that the City is estopped at  this  time

from requiring the Appellants to implement corrective fire protection  for  the

area in question.  In order for estoppel against the City  to  apply,  Appellants

must prove that they relied in good faith on some act or omission made  by  the

City and, because of such reliance, incurred a substantial change  in  position

or extensive obligations and expenses.  Further, the Appellants  must  show  that

the public's interest would not be unduly affected by enforcement  of  such

estoppel.  City of Eden Prairie v. John-Lipke, (decision of  Minnesota  Court  of

Appeals, April 3, 1987); Ridgewood Development Co. v. State, 294  N.W.2d  288

(Minn. 1980); Mesaba Aviation v. County_of Itasca, 258 N.W.2d 877 (Minn,

1977).  The Appellants have a heavy burden of proof    They must first show  the

City's wrongful conduct and then demonstrate that the equities proposed  by  the

Appellants outweigh the public interest.  Ridgewood, 294  N.W.2d  292;  Mesaba,

258 N.W.2d at 880.  See also, Brown-v.  Minnesota Dept.  of  Public Welfare,  368

N.W.2d 906 (Minn. 1985).

 

    In this case, the City did not make specific  affirmative  representations

that the area in question satisfied applicable fire  protection  requirements.

Instead, the Appellants argue that the City's general approval of  the  plans

submitted through the permit process and the City's failure or omission in

pointing out the need for corrective action until construction had been

completed served as the representations upon which the  Appellants  relied.  The

Judge does not find this argument persuasive.  The City's  approval  of  the

plans is qualified by a provision which holds the Appellants  responsible  for

full compliance with applicable code requirements and specifically  states  that

the City's approval is not construed as an affirmative approval of all

compliance issues.  The sprinkler subcontractor was  further  informed  that

approval of the system would not be final until after an  on-site  inspection.

Thus, no representations or omissions were made by the City upon which the

Appellants could attach an estoppel argument.

 

    Further, even if such representations could be proven, the  Appellants  have

failed to show that they have or would incur a detriment which  would  outweigh

the public safety factors, that is, the risk to the public associated  with  the

 

                                       7 -

 


use of the foam plastics in the supermarket inadequately protected by a

thermal barrier or sprinklering system.  The estimate of costs to be incured

by the Appellants in correcting this matter was approximately $11,000.  The

total estimated cost of the construction project was $1,000,000.  This cost

difference does not amount to a "substantial" expenditure as contemplated by

the Ridgewood case such that it would be highly inequitable to require the

 apellants to take such action.

 

                                     P C. E